Product name : HV cable sheath fault locator

Display : Digit Display

Accuracy : ±0.01%-0.03%

Material : Aluminum Alloy

Feature : Reliable

Operating Temperature : -20-60.C

Contact Now

Product Description

Product name Cable sheath fault pinpoint locator
Power 220V(1+10%),50Hz(1+5%)
Output voltage 0~10kV(Square wave)
Output current max 200mA
Output capacity 2kVA
Frequency adjust Min:0.4Hz,Max:1Hz(range adjustable)

With the full deployment of the urban network transformation, many power supply bureaus, construction parties, and even design units encountered 110kV XLPE cables for the first time. Due to time constraints and insufficient experience, many cables failed to pass the withstand voltage test (10kV/ 1min).

At present, most of the outer sheath is made of HDPE sheath material, which has passed the DC 25kV/5min withstand voltage test in the factory, and the leakage current is as low as tens of μA. Therefore, most of the defects after laying are caused by external force damage during laying, including soil filling and cover. Defects after operation usually include termite bites; water in the grounding box; deterioration of the original defect; moisture penetration of the bifurcated part of the grounding wire reduces the insulation resistance, etc., sometimes because the cable is buried too deep or the surrounding conditions are complicated, so It is very difficult to locate, and some defects cannot be resolved after many years, leaving hidden dangers to the operation.
The output voltage of the high-voltage cable outer sheath fault detector is 10KV and below, which fully meets the Chinese national standard GB50150-2006 cable outer sheath withstand voltage test regulations, including the cable outer sheath handover test and preventive test suitable for cross-interconnect systems And the fault location of the outer sheath of the cable. Quickly and accurately find hidden dangers of 10kv-500kv single-core and three-core high-voltage and ultra-high voltage cable outer sheath grounding faults and large leakage currents.
At the same time, it can perform 5kv-10kv on high-density polyethylene and polyvinyl chloride cable outer sheaths, 1 The minute DC withstand voltage test is a special instrument necessary for the maintenance of cable equipment of 10kv-500kv single-core and three-core high-voltage and ultra-high voltage cable operation units, ultra-high voltage cable engineering companies, and various power transmission and transformation engineering companies.
Factory Direct Sales Pull-rod Cable Fault test Cable Outer Sheath Fault Locator
Main features
Voltage adjustable. Frequency adjustable. Over current protection. Pin-pointing and withstand testing switched by one button , the receiver sensitivity can be adjust. Signal frequency adjustable, and zero protection. The test range without blind area The receiver sensitivity is adjustable Signal frequency is adjustable
On-site testing
Factory Direct Sales Pull-rod Cable Fault test Cable Outer Sheath Fault Locator



China Factory Direct Sales Pull-rod Cable Fault test Cable Outer Sheath Fault Locator wholesale

Factory Direct Sales Pull-rod Cable Fault test Cable Outer Sheath Fault Locator Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Xi'an Xu&Hui Electromechanical Technology Co., Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)